Main Field

Testing Laboratories

Valid Since:May 15 , 2026

Type of Activity Test Materials / Products Test Name Test Method Status
Performance Testing of Electrical Appliances
  • Electrical and Mechanical
  • Ducted Air Conditioners
  • Dry Bulb Temperature of Air Leaving Equipment:[-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Entering Water Temperature: [-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Leaving Water Temperature: [-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Water Flow Rate: [1 GPM - 50 GPM]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Volume Flow Rate of Air: [200 CFM - 10000 CFM]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Power Input To Equipment : [0 kW - 30 kW]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Static Pressure: [0 inH2O - 5 inH2O]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Barometric Pressure: [80kPA - 120kPA]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Cooling Capacity: [0.5 TR - 10 TR]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Energy Efficiency %[Derived From Calculations]
ISO 13253, SASO 2682, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358/Amd 1 , SASO 2874, UAE.S5010-5, UAE.S5010-1, AHRI 210/240, AHRI 340/360, ASHRAE-37, ASHRAE-79, AHRI 440, AHRI 1360, AHRI 1230, ASHRAE 127, IEC 60335-2 40 , IEC 60335-1, AActive
  • Non-Ducted Air Conditioners
  • Dry Bulb Temperature of Air Leaving Equipment:[-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Entering Water Temperature: [-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Leaving Water Temperature: [-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Water Flow Rate: [1 GPM - 40 GPM]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Volume Flow Rate of Air: [200 CFM - 10000 CFM]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Power Input To Equipment : [0 kW - 30 kW]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Static Pressure: [0 inH2O - 5 inH2O]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Barometric Pressure: [80kPA - 120kPA]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Cooling Capacity: [0.5TR - 6TR]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Energy Efficiency %[Derived From Calculations]
SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, ISO 5151, SASO 2874, SASO 2681, UAE.S ISO 5151, UAE.S5010-5, UAE.S5010-1, AHRI 440, ASHRAE-79, ASHRAE-37, AHRI 1230, AHRI 1360, ASHRAE 127, IEC 60335 2 40, IEC 60335 1, AHRI 390, AHRIActive
  • Packaged Air Conditioner
  • Measurement Range of Dry Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Dry Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Volume Flow Rate of Air and All Relevant for its Calculations: [1000 CFM - 20,000 CFM]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Power Input To Equipment: [5 kW - 720 kW]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Barometric Pressure: [321 inH2O - 642.34 inH2O]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Static Pressure: [0 inH2O - 4 inH2O]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Measurement Range of Cooling Capacity: [6 TR - 40 TR]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Energy Efficiency %[Derived From Calculations]
ISO 13253, UAE.S5010-5, UAE.S5010-1, ASHRAE-37, SASO 2682, SASO 2874, SASO 2663, SASO ISO 16358-1, ISO 16358-1/Cor 1, ISO 16358-1/Amd 1, AHRI 340/360, AHRI 210/240, AHRI 1360, AMCA 210, ASHRAE 127, IEC 60335 2 40, IEC 60335 1 , AHRI 341/361-0B/1B, AHActive
  • Air Handling Units
  • Entering Water Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [1 GPM - 100 GPM]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Dry Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Leaving Equipment: [-8°C - 60°C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Dry Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Volume Flow Rate of Air and All Relevant for its Calculations: [1000 CFM - 20,000 CFM]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Power Input To Equipment: [5 kW - 720 kW]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Barometric Pressure: [321 inH2O - 642.34 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Static Pressure: [0 inH2O - 4 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Cooling Capacity: [6 TR - 40 TR]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Air Cooled Packaged Chillers
  • Entering Water Temperature: [0°C - 60°C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [0 °C - 60 °C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Condenser Entering Temperature: [0 °C - 60 °C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [41 GPM - 1200 GPM]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 642 inH2O]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Power Input To Equipment: [5 kW - 720 kW]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Cooling Capacity: [4 TR - 410 TR]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
Electrical/mechanical
  • Packaged Air Conditioner
  • Orientation of the unit is Vertical NOT Horizontal
  • AHRI-390 Doc-048-15
Active
  • Packaged Air Conditioner + Ducted Air Conditioner
  • Same setup and test method, only tested at higher ambient temperature.
  • AHRI-341/361-0B/1B Doc-046-15+ Doc-048-15
Active
  • Ducted Air Conditioner
  • Applicable for ducted split units with maintaining the refrigerant parameters only. New test method added
  • AHRI-365 Doc-096-25
Active